Try out the monitoring and supervision system of a real PV system right now,
in real time
Single-Phase Energy Manager Clever - Components
- 230Vac 50Hz single-phase power supply protected by fuse and overvoltage circuit breaker
- Maximum absorbed power 5W
- Analog measurement of two active powers by means of 2 analog inputs to measure the current by CT and 1 input, that is common to both power measurements, to measure voltage by TV. 0.2% precision of the configured full scale.
- Maximum effective current measured by CT: 60 Arms / maximum cable diameter: 8.5 mm
- 1 digital relay output, 1 exchange contact, 230Vac 5A max
- 2 free digital contacts suitable for photosensors to read the meter
- 2 digital inputs suitable for connection to a free contact. These 2 inputs could also be used, with a different configuration, as analog inputs for measuring the temperature by NTC, 10 bit resolution.
- All the connections are secured by screw clamps
- 1 USB input for updating the instrument
- Interface to the local network and internet by LAN, WIFI or GPRS/3G
- 868 MHz radio interface for communicating with the CLEVER VIEW user interface
- Discreet design plastic case for mounting on a 4-module DIN bar
- +5 V DC power feed
- Maximum absorbed power 2W by USB connector
- Backup power by single-cell 400 mAh lithium battery, rechargeable in 5 hours
- 3.5” TFT display rear lit by led
- Resistive Touchscreen
- 868 MHz radio interface for connection to the CLEVER
- Polycarbonate case measuring 150 x 110 mm, 28 mm thick, with table stand or wall fitting
- Glossy black colour
- Maximum current, effective (and peak) current CT 60 Arms
- Calibrated at 0.15% with phase correction on CLEVER
- DC current tolerated without affecting the readings
- Cable length 1,200 mm
- Maximum cable diameter 8.5 mm
- Size 37 mm x 75 mm, d 18 mm
Device equipped with photo-diode for reading the production and/or grid meter.
Available in the wired or 868 MHz radio version
- For use when there is a poor signal from the access point
- Adhesive film attachment on the outside of the electric control panel
- Cable length 400 mm
- Size 115 x 20 mm, 5 mm thick
- Gain 6 dBi
- For use when there is poor coverage by the GPRS signal
- Antenna base with magnet for attaching to a metal base, or adhesive film for attaching to the outside of the electric control panel
- Cable length 3,000 mm
- Size base diameter 30 mm, h = 300 mm
- Gain 3 dB
- Preconfigured for interface with CLEVER BOX WiFi
- Wireless conformity IEEE 802.11b IEEE 802.11g IEEE 802.11n
- LAN conformity IEEE 802.3IEEE 802.3uIEEE 802.1xIEEE 802.1q
- Wireless encryption WEP Encryption-64/128 bit WPA Personal (WPA-PSK using TKIP or AES) WPA Enterprise (WPA-EAP using TKIP) 802.1x Authenticator 802.1x Supplicant-MD5/TTLS (CB & CR mode) Hide SSID in beacons
- Support ip IPv4
- Optional antenna connector SMA-Reverse
- Maximum height 26 mm
- Maximum width 123 mm
- Maximum depth 105 mm
- 4 LAN ports
- LAN speed 10/100 Mbps IEEE 802.3 IEEE 802.3u IEEE 802.3x IEEE 802.1x
- Wan Fast Ethernet connection
- Backup wan Dynamic IP Static IP PPPoE 802.1X + Dynamic IP 802.1X + Static IP L2TP PPTP
- IPv4 support
- Integrated firewall YES
- Vpn support YES
- CE, RoHS, SFT, EMC conformity declarations
- Maximum width 165 mm
- Maximum depth 108 mm
- Maximum height 28 mm