Try out the monitoring and supervision system of a real PV system right now,
in real time
Three-Phase Energy Manager Clever - Components
POWER SUPPLY
- Power 100-240VAC 50/60Hz max. 0,1 A
- Max. intake power 10 W
- Protected by 500mA fuse
INPUTS
- 6 inputs for Ampere transformer 1/2500, max. measurable current
- 60 Arms with Power Sensor CCP00M00 suggested up to 30 kW
- 250 Arms with Power Sensor CCP00100 suggested up to 100 kW
- 500 Arms with Power Sensor CCP00200 suggested up to 200 kW
- Higher powers on request
- 2 digital inputs for 5V pulse meters, input impedance 1K
- 5 analog inputs for NTC 10K sensor, optionally configured initially as signal digital inputs 0-5 V; 0-10 V; 4-20 mA OUTPUTS
OUTPUTS
- 5 contact relay resistive outputs NA 230 VAC max 6 A, one being for exchange
MEASUREMENTS
- Analog active and reactive power and energy measurement and power factor measurement for 6 three-phase production and exchange lines, both as a total for the 3 phases and by single phase
- 0.6% full scale precision along the entire measurement chain (CTs + Clever)
- Measurement of the harmonic current and voltage content by phase
- Measurement of the neutral current
INTERNAL MEMORY
- 8 MBytes flash memory
- The data are sampled, totalled and stored internally every 5 minutes, 60 minutes, 24 hours, 1 month, 1 year. On every link, they are downloaded to the WEB CENTER and PC VIEW computer, where they remain available indefinitely, and they can also be stored locally for up to 10 years.
OTHER INTERFACES
- RS 485 for inverter interface in standard MODBUS mode
- USB 2.0 with software interface for loading programs and configuration data from a USB flash
- Standard communication with local CLEVER devices with 868 MHz radio transmission
- Internal antenna
- Transceiver power 10 dBm
- Interface to the local network and internet by LAN, WIFI or GPRS.
CHASSIS
- Discreet design plastic case for mounting on 9-module DIN bar
- Connections with screw clamps (extractable for the relays)
- +5 V DC power feed
- Maximum absorbed power 2W by USB connector
- Backup power by single-cell 400 mAh lithium battery, rechargeable in 5 hours
- 3.5” TFT display rear lit by led
- Resistive Touchscreen
- 868 MHz radio interface for connection to the CLEVER
- Polycarbonate case measuring 150 x 110 mm, 28 mm thick, with table stand or wall fitting
- Glossy black colour
- Maximum current, effective (and peak) current CT 60 Arms
- Calibrated at 0.15% with phase correction on CLEVER
- DC current tolerated without affecting the readings
- Cable length 1,200 mm
- Maximum cable diameter 8.5 mm
- Size 37 mm x 75 mm, d 18 mm
CCP00100
- Effective (and peak) current 250 Arms suggested up to 100 kW
- Precision 1.0% f.s.
- Tolerates DC current without affecting the reading
- Secondary in screw terminal block
- Maximum cable diameter 28.00 mm
- Size: 105 mm x 57 mm; D 67 mm
CCP00200
- Effective (and peak) current 500 Arms suggested up to 200 kW
- Precision 1.0 % f.s.
- Tolerates DC current without affecting the reading
- Opening
- Secondary in screw terminal block
- Square hole for bars measuring max. 81 x 31 mm square
- Size: 150 mm x 80 mm; D 60 mm
CCP00400
Higher powers available on request.
Device equipped with photo-diode for reading the production and/or grid meter.
Available in the wired or 868 MHz radio version
- For use when there is a poor signal from the access point
- Adhesive film attachment on the outside of the electric control panel
- Cable length 400 mm
- Size 115 x 20 mm, 5 mm thick
- Gain 6 dBi
- For use when there is poor coverage by the GPRS signal
- Antenna base with magnet for attaching to a metal base, or adhesive film for attaching to the outside of the electric control panel
- Cable length 3,000 mm
- Size base diameter 30 mm, h = 300 mm
- Gain 3 dB
- Preconfigured for interface with CLEVER BOX WiFi
- Wireless conformity IEEE 802.11b IEEE 802.11g IEEE 802.11n
- LAN conformity IEEE 802.3IEEE 802.3uIEEE 802.1xIEEE 802.1q
- Wireless encryption WEP Encryption-64/128 bit WPA Personal (WPA-PSK using TKIP or AES) WPA Enterprise (WPA-EAP using TKIP) 802.1x Authenticator 802.1x Supplicant-MD5/TTLS (CB & CR mode) Hide SSID in beacons
- Support ip IPv4
- Optional antenna connector SMA-Reverse
- Maximum height 26 mm
- Maximum width 123 mm
- Maximum depth 105 mm
- 4 LAN ports
- LAN speed 10/100 Mbps IEEE 802.3 IEEE 802.3u IEEE 802.3x IEEE 802.1x
- Wan Fast Ethernet connection
- Backup wan Dynamic IP Static IP PPPoE 802.1X + Dynamic IP 802.1X + Static IP L2TP PPTP
- IPv4 support
- Integrated firewall YES
- Vpn support YES
- CE, RoHS, SFT, EMC conformity declarations
- Maximum width 165 mm
- Maximum depth 108 mm
- Maximum height 28 mm